Electric Heat Tracing Product Features
Principle
After power is turned on (note: the end core wires must not be connected), current flows from one core wire through the conductive PTC material to the other core wire, forming a circuit. The electrical energy heats the conductive material, causing its resistance to increase. When the temperature of the core tape rises to a certain value, the resistance becomes so large that it almost blocks the current, and the temperature no longer rises. At the same time, the electric heat tracing transfers heat to the heated system with a lower temperature.The power of the electric heat tracing is mainly controlled by the heat transfer process, automatically adjusting the output power according to the temperature of the heated system, while traditional constant power heaters do not have this function
.
3 Product Features
2. Temperature range: maximum exposure temperature 85°C, maximum working temperature 65±5°C, minimum working temperature -60°C. 1. Heat tracing structure: inner layer of conductive thermoplastic, outer layer of double-layer flame-retardant polyolefin with shielding layer
3. Installation temperature: minimum: -5°C
4. Thermal stability: after 300 cycles between 10°C and 99°C, the heat output of the heat tracing remains above 90%.
5. Bending radius: 25.4mm at room temperature of 20°C, 35.0mm at low temperature of -30°C
6. Insulation resistance: for a heat tracing length of 100m at an ambient temperature of 20°C, measured with a 2,500VDC megger for 1 minute, the insulation resistance (between conductor and shield) is at least 20MΩ
7. Starting current (10°C): 0.4A per meter
8. For installation and use, please refer to the precautions section
9. Maximum use length: not exceeding 100 meters